NAYY
- Details
- Hits: 6725
Distribution cables of rated voltage 0.6/1k V
Designation: | Standard: |
NAYY | HD 603 S1 3G-2, IEC 60502, DIN VDE 0276-603 |
PP00-AY | MKS N.C3.220 |
Application:
The cable is suitable for fixed installation in free air, in ground, in watter, cable ducts, power stations, if no mechanical damage is to be expected.
Construction:
1 - Conductor: stranded aluminium wires (round and sector shaped), with or without signal/control copper conductor.
2 - Insulation : PVC compound DIV 4 correspond to HD 603-1.
3 - Filler : Epdm rubber or polyester tape
4 - Sheathing material: PVC compound DMV 5 to HD 603-1.
Technical data:
Number of cores, nominal cross cectional area mm² |
Conductor shape | Maximum resistance of conductor at 20⁰C | Overall diameter (approx.) | Rated current-carrying capacity in earth | Rated current-carrying capacity in air | Total net weight(approx.) | Packing – drum |
Number x mm² | Ω/km | mm | A | A | kg/km | m | |
1x16 | RM | 1.91 | 11.5 | - | - | 145 | 1000 /N⁰9 |
1x25 | RM | 1.20 | 12.8 | 160 | c | 196 | 1000 /N⁰9 |
1x35 | RM | 0.868 | 13.7 | 193 | 135 | 250 | 1000 /N⁰10 |
1x50 | RM | 0.641 | 15 | 230 | 166 | 290 | 1000 /N⁰10 |
1x70 | RM | 0.443 | 17 | 283 | 210 | 393 | 1000 /N⁰10 |
1x95 | RM | 0.320 | 19 | 340 | 259 | 510 | 1000 /N⁰12 |
1x120 | RM | 0.253 | 20.2 | 389 | 302 | 601 | 1000 /N⁰13 |
1x150 | RM | 0.206 | 22.1 | 436 | 345 | 712 | 1000 /N⁰13 |
1x185 | RM | 0.164 | 25 | 496 | 401 | 884 | 1000 /N⁰14 |
1x240 | RM | 0.125 | 28 | 578 | 479 | 1100 | 1000 /N⁰15 |
1x300 | RM | 0.100 | 30.4 | 656 | 555 | 1440 | 1000 /N⁰16 |
1x400 | RM | 0.0778 | 34 | 756 | 653 | 1812 | 500 /N⁰14 |
4x16 | RM | 1.91 | 22 | - | - | 698 | 500 /N⁰10 |
4x25 | RM | 1.20 | 25.6 | 102 | 82 | 950 | 500 /N⁰12 |
4x35 | RM | 0.868 | 29.8 | 123 | 100 | 840 | 500 /N⁰13 |
4x35 | SM | 0.868 | 28 | 123 | 100 | 790 | 500 /N⁰12 |
4x50 | SM | 0.641 | 31 | 144 | 119 | 1030 | 500 /N⁰13 |
4x70 | SM | 0.443 | 35.9 | 179 | 152 | 1470 | 500 /N⁰15 |
4x95 | SM | 0.320 | 39.2 | 215 | 186 | 1880 | 500 /N⁰15 |
4x120 | SM | 0.253 | 44 | 245 | 216 | 2292 | 500 /N⁰16 |
4x150 | SM | 0.206 | 47 | 275 | 246 | 2740 | 500 /N⁰18 |
4x185 | SM | 0.164 | 51 | 313 | 285 | 3300 | 500 /N⁰20 |
4x240 | SM | 0.125 | 56 | 364 | 338 | 4600 | 500 /N⁰20 |
4x16+1.5 | RM+RE | 1.91/12.1 | 22 | - | - | 718 | 500 /N⁰10 |
4x25+1.5 | RM+RE | 1.20/12.1 | 25.6 | 102 | 82 | 970 | 500 /N⁰12 |
4x35+1.5 | RM+RE | 0.868/12.1 | 29.8 | 123 | 100 | 860 | 500 /N⁰13 |
4x35+1.5 | SM+RE | 0.868/12.1 | 28 | 123 | 100 | 810 | 500 /N⁰12 |
4x50+1.5 | SM+RE | 0.641/12.1 | 31 | 144 | 119 | 1050 | 500 /N⁰13 |
4x70+1.5 | SM+RE | 0.443/12.1 | 35.9 | 179 | 152 | 1490 | 500 /N⁰15 |
4x95+1.5 | SM+RE | 0.320/12.1 | 39.2 | 215 | 186 | 1900 | 500 /N⁰15 |
4x120+1.5 | SM+RE | 0.253/12.1 | 44 | 245 | 216 | 2312 | 500 /N⁰16 |
4x150+1.5 | SM+RE | 0.206/12.1 | 47 | 275 | 246 | 2760 | 500 /N⁰18 |
4x185+1.5 | SM+RE | 0.164/12.1 | 51 | 313 | 285 | 3320 | 500 /N⁰20 |
4x240+1.5 | SM+RE | 0.125/12.1 | 56 | 364 | 338 | 4620 | 500 /N⁰20 |
Nominal voltage | 0.6/1 kV |
Test voltage | 4 kV |
Highest operating temperature | +70⁰C |
Short circuit temperature (5s) | 160⁰C for cross sections area ≤300mm² |
Short circuit temperature (5s) | 140⁰C for cross sections area ≥300mm² |
Minimum banding radius | 12x cable diameter |
Colour of jacket | Black |
RM – multiwire round stranded conductor
SM - multiwire sector stranded conductor
RE – solid round conductor