NAY2Y

NAY2Y

Distribution cables of rated voltage 0.6/1k V

 

 

Designation: Standard:
NAY2Y HD 603 S1 3G-2, IEC 60502-1, DIN VDE 0276-603           
PP00-AY                             MKS  N.C3.220

 

Application:

For fixed installation, in power plants, in outdoor applications, for indoor installations, underground, in water. The cables are resistant to UV radiation.

 

Construction:

1 - Conductor: -    stranded aluminium wires (round and sector shaped), with or without signal/control  copper conductor. 
2 - Insulation : PVC compound DIV 4 correspond to HD 603-1.
3 - Filler : Epdm rubber or polyester tape
4 - Sheathing material: HDPE compound DMP 2 to HD 603-1.
 

Technical data:

Number of cores, nominal cross cectional area
mm²
Conductor shape Maximum resistance of conductor at 20⁰C Overall diameter (approx.) Rated current-carrying capacity in earth Rated current-carrying capacity in air Total net weight(approx.) Packing – drum
Number x mm²   Ω/km mm A A kg/km m
1x16 RM 1.91 11.5 - - 132 1000 /N⁰9
1x25 RM 1.20 12.8 160 110 162 1000 /N⁰9
1x35 RM 0.868 13.7 193 135 211 1000 /N⁰10
1x50 RM 0.641 15 230 166 255 1000 /N⁰10
1x70 RM 0.443 16.8 283 210 343 1000 /N⁰10
1x95 RM 0.320 18.8 340 259 468 1000 /N⁰12
1x120 RM 0.253 20 389 302 537 1000 /N⁰13
1x150 RM 0.206 21.9 436 345 638 1000 /N⁰13
1x185 RM 0.164 24.8 496 401 780 1000 /N⁰14
1x240 RM 0.125 27.8 578 479 989 1000 /N⁰15
1x300 RM 0.100 30.2 656 555 1233 1000 /N⁰16
1x400 RM 0.0778 33.8 756 653 1534 500 /N⁰14
4x16 RM 1.91 22 - - 602 500 /N⁰10
4x25 RM 1.20 25.6 102 82 704 500 /N⁰12
4x35 RM 0.868 29.8 123 100 832 500 /N⁰13
4x35 SM 0.868 28 123 100 797 500 /N⁰12
4x50 SM 0.641 31 144 119 1004 500 /N⁰13
4x70 SM 0.443 35.7 179 152 1415 500 /N⁰15
4x95 SM 0.320 39.0 215 186 1855 500 /N⁰15
4x120 SM 0.253 43.8 245 216 2145 500 /N⁰16
4x150 SM 0.206 46.8 275 246 2711 500 /N⁰18
4x185 SM 0.164 50.8 313 285 3287 500 /N⁰20
4x240 SM 0.125 55.8 364 338 4158 500 /N⁰20
4x16+1.5 RM+RE 1.91/12.1 22 - - 617 500 /N⁰10
4x25+1.5 RM+RE 1.20/12.1 25.6 102 82 719 500 /N⁰12
4x35+1.5 RM+RE 0.868/12.1 29.8 123 100 847 500 /N⁰13
4x35+1.5 SM+RE 0.868/12.1 28 123 100 812 500 /N⁰12
4x50+1.5 SM+RE 0.641/12.1 31 144 119 1019 500 /N⁰13
4x70+1.5 SM+RE 0.443/12.1 35.7 179 152 1430 500 /N⁰15
4x95+1.5 SM+RE 0.320/12.1 39.0 215 186 1875 500 /N⁰15
4x120+1.5 SM+RE 0.253/12.1 43.8 245 216 2165 500 /N⁰16
4x150+1.5 SM+RE 0.206/12.1 46.8 275 246 2731 500 /N⁰18
4x185+1.5 SM+RE 0.164/12.1 50.8 313 285 3307 500 /N⁰20
4x240+1.5 SM+RE 0.125/12.1 55.8 364 338 4178 500 /N⁰20

 

Nominal voltage  0.6/1 kV
Test voltage 4 kV 
Highest operating temperature   +70⁰C
Short circuit temperature (5s) 160⁰C for cross sections area ≤300mm²
Short circuit temperature (5s)           140⁰C for cross sections area ≥300mm²
Minimum banding radius           12x cable diameter
Colour of jacket         Black

 

RM – multiwire round stranded conductor
SM - multiwire sector stranded conductor
RE – solid round conductor
 
link directory